Experiment No.: – 17
Aim of the Experiment: –
To study load test on single phase transformer and determine efficiency and voltage
regulation of a single phase transformer.
Apparatus Required: –
| Sl. No. | Name | Specification | Quantity |
|---|---|---|---|
| 1 | Single-phase Auto-transformer | (0-270)V, 3KVA, 30A | 1 no. |
| 2 | Singe Phase Transfoormer | 230/230, 3 KVA | 1 no. |
| 3 | Wattmeter | (0-150/300/600)V, 10A/20A, Dynamometer type, UPF | 1 no. |
| 4 | Ammeter | (0-5/10/20)A, MI | 1 no. |
| 5 | Voltmeter | (0-150/300/600)V, MI | 1 no. |
| 6 | Resistive Load | 2 KW | 1 no. |
| 7 | Connecting Wire | PVC Insulated Copper | As per required |
Circuit Diagram: –

Theory: –
When the secondary winding of a transformer is connected to a load and a voltage V is
applied to the primary winding, the transformer is said to be operated under load condition. Under this condition transformer cupper loss increases with increase in current . So efficiency changes. Maximum efficiency point reaches when Iron loss is equal to copper loss. Iron loss is constant for a transformer, therefore at maximum point copper loss is very less & equal to iron loss. Near to half load efficiency reaches to next peak point & it gradually decreases when further load increases. When load increases beyond half load copper loss will increase which reduces the efficiency. This situation happens when transformer is distribution type transformer.

Precautions: –
- Do not switch on supply without concerning respected teachers.
- Single phase Auto transformer must be kept at minimum potential point.
- Primary voltage that is V1 should always be constant throughout the experiment.
Procedures: –
- Make the connection as shown in the diagram keeping the auto-transformer in zero
position and all switches and load is in off position.
- Switch on the AC supply and then vary the voltage up to rated voltage of the transformer.
- Now, start loading the transformer by putting on load switch on. So that a suitable current is obtained.
- And then change the load and note down the reading of all the instrument.
- Here the primary voltage of the transformer should always be in rated voltage
irrespective of load.
Observation Table for Open Circuit Test: –
| Sl. No. | Load in Watts. | V1 in Volts. | I1 in Amps. | W1 in Watts. | V2 in Volts. | I2 in Amps. | W2 in Watts. | % Efficiency | % Voltage Regulation |
|---|---|---|---|---|---|---|---|---|---|
| 1 | |||||||||
| 2 | |||||||||
| 3 | |||||||||
| 4 | |||||||||
| 5 | |||||||||
| 6 | |||||||||
| 7 | |||||||||
| 8 | |||||||||
| 9 | |||||||||
| 10 |
Calculations:
Conclusion: –
To be written by Student.